Automatic Mains Failure Control Panels :
|
|
• |
The Automatic Mains Failure Control Panels is designed to monitor (& to start Generator automatically) the mains source and upon partial or full failure of the source / Main supply. |
• |
When mains fail, then it is sensed by Line Voltage Monitor (L.V.M.) and three starting pulses are given to Genset. |
• |
If Genset does not start within three attempts, then ‘Starting Failure’ alarm is sounded and stop signal is given to Genset to stop it fully & no start signals are given further. |
• |
If Genset starts within three attempts, then remaining starting pulses are automatically cut-off. |
• |
When Genset starts successfully, it builds up the rated voltage and Genset contactor/breaker is closed automatically. The load then is switched on / transferred to the Genset. |
• |
When Mains restores, which is checked by L.V.M. for its healthiness, the generator is then disconnected from the load and automatic transfer back to the mains source takes place, with the generator running on a cool down period and resetting ready for next failure. Load is now connected to the mains. |
|
|
| |
|
|
• |
Genset is then run for about 5 minutes time set, on no load and it is stopped automatically. |
• |
The cycle can be repeated if Mains fail again |
• |
Safeties like L.L.O.P., H.W.T. and over speed (optional) are operative when the Genset is
|
• |
Running. For any of the above faults, Genset stops immediately.
|
• |
Additional safeties can be added, if it is a specific requirement of the customer.
|
• |
Automatic function can be totally by-passed and Genset can be started-stopped in manual mode also. |
• |
While the load is connected to Mains, the Genset can be tested for its performance in TEST mode also. In TEST mode, the total automatic cycle can be tested, without closing the Genset breaker. |
|
|
Indication for the following : |
|
Low Oil Press |
High Room Temp. |
Over Speed |
Fail to start |
DC battery REV. POLARITY |
Engine hours run Counter |
RPM |
Frequency AC |
Voltage AC line-neutral |
Voltage AC line-line |
AC current |
Engine Temperature |
|
|
Shutdown Protections : |
|
Low Oil Press |
High Room Temp. |
Over Speed |
Fail to start |
Under speed |
Over current |
V belt failure |
Blower failure |
Earth fault (opt.) |
- |
- |
- |
|
| |
 |
|
Manual Control Panel : |
Technical Specification |
| |
• |
Anual Start Generator Control Panels are designed to operate manually directly on the control panel. The engine control module incorporated as standard is electronic type. |
• |
The Panels are manufactured from 1.5mm sheet steel and painted in stove enamel BLACK textured finish as standard. |
• |
Set mounting format with integral MCCB or separate breaker Panel depending on ratings with an external protection to IP41 with wrap over cover. |
• |
Operating temperature range: -25ºC to 50ºC. |
|
|
|
Each Panel is complete with the following components as standard : |
|
| Voltmeter |
3- Ammeter |
1- Freq. RPM meter |
Fail to start |
1- Battery Voltmeter |
1-Engine hours Run Counter |
1- Oil press. Gauge |
1- Engine temp. Gauge |
3- C.T. above 100 A |
1- voltmeter sel. sw |
1- Electronic Generator Control Module fully Programmable with : Control key switch Off / Run / Start (Optional) |
1- MCB / MCCB |
4- AC and DC fuses |
1- Control terminals 1- Neutral terminal |
1- Set of AV mounts (Optional) |
2- 20/30 amp rated Relays for Fuel and start Solenoids |
|
|
Indicators for the following : |
|
Low Oil Pressure |
High Temp. |
Over Speed |
Fail to start |
Under Speed |
Over current |
V belt failure |
Blower failure |
Earth fault (opt.) |
Control on |
DG on |
- |
Shutdown protections : Low oil pressure |
High room temperature |
Over Speed |
Fail to start |
Under Speed |
Over current |
V belt failure |
Blower failure |
Earth fault (opt.) |
- |
- |
- |
|
Options available on request. |
|
|
|